Electrical circuit breakers manufactured by the Federal Pacific Electric (FPE) Company, and Stab-Lok® models in particular, have the potential to fail to trip in the case of an overload or short-circuit. A circuit breaker that fails to trip or that is conducting electricity after it has been disabled could cause a fire or personal injury.

Federal Pacific Electric panels were installed between the 1950s and approximately 2000. It has been estimated that there are approximately 30 million FPE Stab-Lok® breakers in use in the U.S. In the early 1980s it was confirmed that FPE fraudulently applied Underwriters Laboratories, Inc. (UL) labels to their circuit breakers falsely indicating that the equipment had met UL safety standard requirements. The Consumer Product Safety Commission performed tests on the equipment and determined failure rates in excess when compared to similar equipment produced by other manufacturers. Due to budget constraints preventing conclusive testing, no recall was initiated. It is estimated that thousands of fires each year may be a direct result of malfunctioning FPE panel breakers.

There are several distinct design deficiencies with FPE circuit breaker panel and components that promote unsafe conditions including:

  •  The breaker handles stick out slightly over the dead front cover opening making it difficult to remove the panel cover without tripping the breakers.
  • The set of prongs at the rear of the individual breakers are designed to be inserted into a slot in the rear bus bar, but allow loose metal connections resulting in overheating and arcing. It is not unusual to see scorch marks on the bus bars of FPE equipment once the circuit breakers are removed.
  • The stabs of FPE half size circuit breakers (also called “wafer” breakers) can be bent and forced into sockets designed for full-sized breakers, resulting in an overcrowded panel and loose connections.
  • Having been designed and manufactured several decades ago, the equipment does not meet current codes and standards. The typical FPE panel does not have adequate space resulting in insufficient wire bending space and overcrowding of the wires.

Identification of the presence of FPE equipment is important for the safety of a building and the value of a condition assessment. There are several ways to confirm FPE as the manufacturer of electrical circuit breakers including:

  • The electrical panel will typically display the FPE or related name or logo on the front cover.
  • Stab-Lok® circuit breakers may be marked FPE or Federal Pacific, but may not be marked “Stab-Lok® on the breaker.
  • The name “Stab-Lok® may be printed near the center or side of the inside of the electrical panel, behind the door, or on the door itself.
  • The individual breakers will have a red strip across the front.

Depending on the conditions and type of FPE panel found at a building, replacement of the equipment is typically warranted.